A starter that keeps tripping is not the problem — it is the messenger. The overload relay inside it trips because the motor is drawing more current than it should. Reset it without finding out why, and sooner or later the winding burns.

Safety first: switch off and isolate the supply before opening any starter or panel. If you are not trained to work on live electrical equipment, call an electrician.

First, Note When It Trips

The timing tells you most of the story:

When it trips Most likely cause
The moment you press START Weak capacitor, jammed pump, or a short in the cable
After a few minutes of running Low voltage, overload setting too low, or a single phase missing
Only in the evening Low grid voltage during peak hours
After rain or at night Moisture in the cable joint or starter
Randomly, with a buzzing sound Loose or burnt contacts, low coil voltage

The Eight Real Causes

1. Low voltage

Rural lines often drop well below 400V (three-phase) or 220V (single-phase), especially in the evening. A pump motor doing the same work at lower voltage pulls more current — enough to trip a correctly set relay.

Check: measure voltage at the starter terminals while the motor is running, not at idle. If it sags badly, the starter is doing its job. A voltage-protected panel or an auto switch that waits for healthy supply prevents the trip-reset cycle.

2. One phase missing (single-phasing)

On a three-phase motor, if one phase fails the motor keeps running on two — and overheats fast. The overload relay may trip, or may not trip in time. This is the most common cause of burnt three-phase windings in India.

Check: measure all three phases. A Single Phase Preventer disconnects the motor instantly when a phase drops. Our guide on phase failure protection explains why the overload relay alone is not enough.

3. Overload relay set wrong

If the relay is set below the motor's full-load current (FLC), it trips on normal running. If it is set far above FLC, it never protects at all.

Check: read the FLC (amps) on the motor nameplate and set the relay to that value — never more than about 10% above it.

4. A weak capacitor (single-phase pumps)

A single-phase motor needs its capacitor to start. As a capacitor ages it loses capacitance; the motor struggles, takes longer to reach speed, and draws heavy current while doing so.

Check: if the motor hums before it starts, or starts only on the second try, test the capacitor. See how to tell when a capacitor has failed.

5. Mechanical load on the pump

Sand and silt in the bore, worn bearings, or a pump set too deep for its rating all make the motor work harder.

Check: if current is high even at good voltage and with all phases present, the problem is in the pump, not the starter.

6. Undersized or long cable

Thin cable over a long run to a deep borewell drops voltage before it reaches the motor — the same effect as low grid voltage.

Check: compare voltage at the starter with voltage at the pump end. A large difference means the cable is too thin for the distance.

7. Loose, burnt or pitted contacts

Loose terminals and worn contactor contacts heat up, chatter, and cause uneven current between phases.

Check: with the supply isolated, look for blackened terminals, melted insulation or pitted contacts. Tighten or replace — never just clean and refit a badly pitted contactor.

8. Moisture or a cable fault

Water in a cable joint or inside the enclosure causes leakage and nuisance trips, often after rain.

Check: an insulation (megger) test on the motor and cable will show it. Use proper resin joint kits for submersible cable.

What Never to Do

  • Don't bypass the overload relay or tie the contacts shut. The motor will run — until the winding burns.
  • Don't keep turning the relay setting up until it stops tripping. You are switching off the only protection the motor has.
  • Don't keep resetting a starter that trips within seconds. Find the fault first.

Choosing Protection That Matches Your Supply